FM-200 & Novec 1230 System Maintenance in Saudi Arabia(Riyadh, Jeddah & Dammam)
Clean-agent suppression protects server rooms, data centres and archives without damaging equipment. We maintain FM-200 and Novec 1230 systems — cylinders, pressure, detection and release controls.
What's included
- Cylinder weight and pressure checks
- Detection and release panel testing
- Room integrity and pipework inspection
- Abort and manual release checks
- Service records and recommendations
Why clean-agent systems need regular service
FM-200 (HFC-227ea) and Novec 1230 (FK-5-1-12) systems sit unused for years — yet they must discharge correctly within seconds when a fire starts. A slow cylinder leak, a blocked nozzle, a disconnected actuator or a new unsealed cable opening in the room wall can each stop the agent reaching and holding its design concentration. Regular inspection catches these silent faults before they matter.
What our FM-200 / Novec 1230 service covers
- Cylinder pressure readings and weight / liquid-level checks against the nameplate charge
- Inspection of valves, solenoid and manual actuators, discharge hoses and pipe supports
- Nozzles checked for blockage, orientation and obstructions
- Detection test: smoke and heat detectors, cross-zone logic and the release panel
- Function test of sounders, beacons, abort and manual release stations — without discharging the gas
- Interface checks: HVAC and damper shutdown, power shutdown and fire alarm signals
- Room walk-through for new openings, door closers and seals
- Service tags, logbook entries and a written report
Room integrity (door fan) testing
A clean-agent system only works if the protected room holds the gas long enough — NFPA 2001 calls for a hold time of at least 10 minutes. After fit-out works, new cable trays or ceiling changes, we recommend a room integrity (door fan) test to confirm the room still meets its design.
Recharge, refill and replacement
If a cylinder has lost charge, has discharged, or is due for its periodic pressure test, we arrange the recharge or replacement and put the system back in service with a full function test and updated records.
Sectors we serve
We serve clients all over Saudi Arabia — mainly Riyadh, Jeddah and Dammam — from our head office in Riyadh.
Frequently asked questions
How often should FM-200 or Novec 1230 systems be serviced?
Clean-agent systems are typically inspected at least every six months, including cylinder pressure and weight checks, in line with NFPA 2001.
Will the inspection set off the gas?
No. The actuators are isolated before testing, so detection, alarms and release signals are proven safely without discharging the agent.
What is the difference between FM-200 and Novec 1230?
Both are clean agents that leave no residue and are safe for electronics. FM-200 (HFC-227ea) is a hydrofluorocarbon; FK-5-1-12, sold as Novec 1230 and under other brand names, has a much lower environmental impact. A system must be refilled with the agent it was designed for.
What happens if a cylinder shows low pressure?
Under NFPA 2001, a cylinder that has lost more than 5% of its agent, or more than 10% of its pressure after temperature correction, must be refilled or replaced. We report it straight away and arrange the recharge.
Do you offer an annual maintenance contract (AMC) for FM-200 & Novec 1230 Maintenance?
Yes. FM-200 & Novec 1230 Maintenance can be covered under a Star House AMC on its own or together with your other building systems in one single contract.
Which areas do you cover?
We serve clients all over Saudi Arabia — mainly Riyadh, Jeddah and Dammam — from our head office in Riyadh.